102
CET Electric Technology
5.
Return to the
Branch Setup
page by selecting
Branch Setup
on the left-hand pane to configure
Voltage Phase
and
CT Ratio
for each SM
according to the actual wiring at site.
6.
Configure
Breaker Rating
by selecting
Breaker Rating Setup
on the left-hand pane.
Note:
The Breaker Rating range for Mains and Branch Inputs is between 1 and 10,000A.
Figure 4-41 Breaker Rating Setup page
The PMC-592 with Firmware V1.00.10 or later supports of customizing 2-Ø and 3-Ø SMs via the optional
HMI (Firmware V1.02.01 or V1.03.05) via
Setup => Basic Setup (Page 5).
Figure 4-42 Custom SM pages
4.6 Virtual Meters (VM)
The PMC-592 with Firmware V1.00.09 or earlier supports up to ten Virtual Meters (VM1 to VM10) which
can be used to perform arbitrary aggregation (Addition only) from any of the 84 individual 1-Ø SMs. The
following figure is an example of 3 Virtual Meters:
Figure 4-43 Virtual Meter Example