143
CET Electric Technology
6885
RW
SM2 CT Polarity
UINT16
1 = Reversed
6889
RW
SM3 CT Polarity
UINT16
6887
RW
SM4 CT Polarity
UINT16
…
…
6967
RW
SM84 CT Polarity
UINT16
Table 5-73 SM CT Setup
5.8.6.4 2-Ø and 3-Ø SM Customization Setup
Register
Property
Description
Format
Range/Options
52300
RW
SM Customization Enable
UINT16
0 =Disabled*, 1 = Enabled
52301~52302
RW
2-Ø SM1 Parameters
+0: 1-Ø SM #x
UINT16x2
x: 1 to 84
+1: 1-Ø SM #y
UINT16x2
y: 1 to 84
52303~52304
RW
2-Ø SM2 Parameters
UINT16x2
See 2-Ø SM1 Parameters
52305~52306
RW
2-Ø SM3 Parameters
UINT16x2
…
…
…
UINT16x2
52383~52384
RW
2-Ø SM42 Parameters
UINT16x2
52385~52387
RW
3-Ø SM1 Buffer
+0: 1-Ø SM #x
UINT16x3
x: 1 to 84
+1: 1-Ø SM #y
UINT16x3
y: 1 to 84
+2: 1-Ø SM #z
UINT16x3
z: 1 to 84
52388~52390
RW
3-Ø SM2 Parameters
UINT16x3
See 3-Ø SM1 Parameters
52391~52393
RW
3-Ø SM3 Parameters
UINT16x3
…
…
…
…
52466~52468
RW
3-Ø SM28 Parameters
UINT16x3
Table 5-74 2-Ø and 3-Ø SM Customization
5.8.7 VM (Virtual Meter) Setup
5.8.7.1 VM Configuration
Register
Property
Description
Format
Range/Options
6700-6705
RW
VM1 Configuration
UINT16
See Note 1)
VM Configuration Data Structure
6706-6711
RW
VM2 Configuration
UINT16
6712-6717
RW
VM3 Configuration
UINT16
6718-6723
RW
VM4 Configuration
UINT16
6724-6729
RW
VM5 Configuration
UINT16
6730-6735
RW
VM6 Configuration
UINT16
6736-6741
RW
VM7 Configuration
UINT16
6742-6747
RW
VM8 Configuration
UINT16
6748-6753
RW
VM9 Configuration
UINT16
6754-6759
RW
VM10 Configuration
UINT16
Table 5-75 Total VM Configuration Group
Notes:
1)
VM configuration data structure
Offset
Property
Description
Format
Range/Options/Default*
+0
RW
VM Configuration 1
2
Bitmap
0* to 65535
+1
RW
VM Configuration 2
2
Bitmap
+2
RW
VM Configuration 3
2
Bitmap
+3
RW
VM Configuration 4
2
Bitmap
+4
RW
VM Configuration 5
2
Bitmap
+5
RW
VM Configuration 6
2
Bitmap
0* to 63
Table 5-76 Total VM Configurations
2)
Each Bit indicates if a particular SM is included in a VM’s aggregation. Setting a bit to 1 includes a SM or to 0 excludes it in the
VM’s aggregation. The Virtual Meter configuration is supported through communications, the built-in Web Interface and the
optional HMI Display.
Bit
Bit 15
Bit 14
Bit 13
…
Bit 2
Bit 1
Bit 0
SMs
SM16
SM15
SM14
…
SM3
SM2
SM1
Table 5-77 VM Configuration 1
Bit
Bit 15
Bit 14
Bit 13
…
Bit 2
Bit 1
Bit 0
SMs
SM32
SM31
SM30
…
SM19
SM18
SM17
Table 5-78 VM Configuration 2