169
CET Electric Technology
c.
Please verify that the power supply is securely connected to the PMC-592 and keep it
powered on during the entire upgrade process. Losing power in the middle of the
firmware upgrade may render the PMC-592 inoperable.
d.
Click
Upgrade
at the bottom of the
Firmware Upgrade
page to initiate the upgrade.
The upgrade process will take about 5 minutes to complete.
e.
When the upgrade is finished, you will be prompted to reboot the PMC-592.
6.
Check the
Firmware Version
by following Step 3 above to confirm that the upgrade is
successful.
7.
Restore the
Factory Defaults
Settings if the PMC-592 is upgraded from V1.00.09 or earlier to
V1.00.11 or later due to some minor incompatibilities for the features enhancement in
V1.00.11. Click
Diagnostics => Maintenance => Factory Defaults
and the following screen
appears on the right-hand pane, then click
Restore.
8.
Restore the previously saved configuration.
a.
Click
Diagnostics => Maintenance => Backup & Restore
on the left-hand pane and
the following screen appears on the right-hand pane. Click
Restore
, select the
previously saved configuration file with the .ini extension and then click
Open
. The