68
CET Electric Technology
Figure 3-39 Communication Setup Interface
3.2.4.5.8 Record Setup
Click
Record Setup
on the left-hand pane and the following screen appears on the right-hand pane
where the Waveform Recorder (WFR), Interval Energy Recorder (IER) and Data Recorder (DR) settings
can be configured. Click
Submit
to save your changes or click
Cancel
to cancel your changes. The
following table describes each parameter.
Parameter
Description
Options/Default*
Waveform Record Setup (WFR)
Waveform Format
Specifies the WRF Format in # of Samples x # of Cycles
64 Samples x 75 Cycles*
64 Samples x 150 Cycles
32 Samples x 75 Cycles
32 Samples x 300 Cycles
16 Samples x 300 Cycles
16 Samples x 600 Cycles
Pre-fault Cycles
Specifies the number of pre-fault cycles.
1 to 10 Cycles, 5*
Trigger Setup
Specifies which event (more than one event can be selected at
the same time) would trigger the Waveform recording.
Dip/Swell
Voltage/Current
Unbalance/Harmonic
Power
Frequency
DI
Energy Log Setup (Interval Energy Recorder)
Recording Mode
Specifies the IER’s (Interval Energy Recorder) Recording Mode.
Disabled*
Stop-When-Full
First-In-First-Out (Circular)
Recording Depth
Specifies the IER’s Recording Depth. This would provide a
maximum energy recording for 35 days @ 5 min, 104 days @ 15
min or 417 days @ 60min.
0 to 10,000*
Recording Interval
Specifies the IER’s Recording Interval.
5mins*
10mins
15mins
30mins
60mins
Start Time
Specifies when to start the IER. This is useful if the user wants to
record the energy consumption for a specific period of time in
conjunction with the Stop-When-Full Recording Mode.
Format: DD/MM/YYYYY HH:MM:SS
Data Log Setup (DR Setup via the Web Interface is available in Firmware V1.00.05 or later)
Data Log #x
Select a Data log for configuration.
Range: Data Log #1 to Data Log #10
Data Log #x Setup
Start Mode
Specify if the selected Data Recorder is enabled.
Disabled*
Enabled
Recording Mode
Specify the recording mode for the selected Data Recorder.
Stop-When-Full*
First-In-First-Out
Recording Depth
Specify the recording depth (i.e. number of logs) for the selected
Data Recorder.
0 to 65535, 52704*