Tariff Switching between T1 and T2~ for Main and GenSet Supply based on the status of a DI
Digital Outputs
o
2 Channels Form A mechanical relays - 5A @ 250VAC / 30VDC
RTD Input
#
o
2 Channels PT100 (sensor not included)
* Available in Firmware V1.00.08 or later
#
Available in Firmware V1.00.04 or later
~ Available in Firmware V1.00.10 or later
Communications
P1/HMI - DB9 Connector
*
Modbus RTU
Compatible with RS-232/422/485
1200 to 38,400 bps
*The P1 connector has been changed from a plug-in terminal to DB9 since Hardware V1.01.00
P2 - RS-485
Modbus RTU
Optically isolated
1200 to 38,400 bps
Optional connection with up to 4 external DI Modules from CET since Firmware V1.00.03
P3 - Ethernet Ports
10/100BaseT
Modbus TCP and Modbus RTU over TCP protocols
HTTP, SMTP, SNTP, SNMP and FTP
Firmware upgrade via Ethernet port
Configurable IP Port No. for HTTP, Modbus TCP and RTU over TCP/IP since Firmware V1.00.10
Time Synchronization
Battery-backed real-time clock @ 6ppm (≤ 0.5s/day)
Time Synchronization via SNTP protocol
System Integration
PecStar iEMS
The PMC-592 is supported by CET’s PecStar iEMS. It can also be easily integrated into other 3rd party
systems with its support of multiple communications ports and different industry standard protocols.
3
rd
Party System Integration
Easy integration into Automation, Energy Management or SCADA systems via Modbus RTU, Modbus
TCP or SNMP
The on-board Web Server allows complete access to its data and supports the configuration for
most of the setup parameters via a web browser without the use of any proprietary software