Conettix Universal Dual Path Communicator
Specifications and certifications | en
97
Bosch Security Systems, Inc.
Installation and Operation Manual
2017.11 | 05 | F.01U.311.207
12.1.2
Application environment
Application
Minimum Required
Standby Time (hr)
Minimum Alarm Time (min)
Residential Burglary
4
4
Proprietary Burglary
4
N/A
Central Station (Bank)
72
N/A
Central Station (Mercantile)
4
N/A
Police Station Connected (Bank)
72
30 (CUL)/15 (UL)
Police Station Connected (Mercantile)
24
30 (CUL)/15 (UL)
Local Burglary (Bank)
72
30 (CUL)/15 (UL)
Local Burglary (Mercantile)
24
30 (CUL)/15 (UL)
Commercial Fire
24
30 (CUL)/5 (UL)
Residential Fire
24
5 (CUL)/4 (UL)
Table
12.18: Minimum standby and alarm times
Notice!
UL Commercial Burglary Application Requirements
Mount the module in the B465 enclosure. If the unit is used in a commercial burglar
environment, and is enclosed in a commercial enclosure, that enclosure must be tampered.
The B465 must be mounted inside an attack resistant enclosure (D8108A) if the installation is
a local or police station connection. For Commercial Burglary applications, house all
communicators in tampered enclosures. You must wire system troubles back to the control
panel as the B46 can not be used in the D8108A enclosure.