102
en | Specifications and certifications
Conettix Universal Dual Path Communicator
2017.11 | 05 | F.01U.311.207
Installation and Operation Manual
Bosch Security Systems, Inc.
12.1.6
Required programming to meet ULC-S304
This section identifies the programming requirements you must make in order to comply with
ULC-S304 Signal Receiving Centre and Premise Alarm Control Units.
Requirement
Parameter
Supervision interval for IP communications
Ethernet Supervision Time,
set to 180 seconds
Cellular Supervision Time,
set to 180 seconds
Communicators are not suitable for active
communication channel (IP)
security and
medium or high risk applications unless such
can be “on line” at all times, have a minimum
128 bit encryption scheme, have encryption
enabled, network and domain security
implemented and are in compliance with
Subsection 15.2, Active Communication
Channel Security.
AES Encryption, Key Size,
set to 128, 192, or 256 bits
Mains power supply below 85% of rated
supply shall be detected and transmitting to
the receiving centre in not more than 3 hours
Primary Power Fail Delay,
set to 0 - 180 minutes
If the signal receiving centre equipment is
completely duplicated with standby
equipment and a switchover can be
accomplished in not more than 90 seconds
with no loss of signals during this period, the
capacity of the system is unlimited otherwise
it shall be limited to 1000 alarm systems
connected to the receiving centre
No special parameters need to be set in the
B465, verify with central station
12.1.7
Required programming to meet ULC-S559
This section identifies the programming requirements you must make in order to comply with
ULC-S559 Fire Signal Receiving Centres and Systems.
Requirement
Parameter
Mains power supply below 85% of rated
supply shall be detected and transmitting to
the receiving centre in not more than 3 hours
Primary Power Fail Delay, page 73
,
set to 0 - 180 minutes
Supervision interval for IP communications
Ethernet Supervision Time, page 61
,
set to 180 seconds
Cellular Supervision Time, page 62
set to 180 seconds