Conettix Universal Dual Path Communicator
Maintenance and troubleshooting | en
83
Bosch Security Systems, Inc.
Installation and Operation Manual
2017.11 | 05 | F.01U.311.207
SYSTEM TROUBLE Flashing (one flash) - Ethernet Trouble
Flash pattern (TX)
Function
Flashing
Indicates an Ethernet Network Cable open. Verify your
Ethernet connection to the B465 is secure. Also verify
the Ethernet connection is secure to your network.
Flashing (two flashes)
Indicates an Ethernet IP Address error Verify that DHCP
is enabled if your network is assigning the IP address or
that your network administrator has setup your device
correctly. Refer to USB menu options to change/edit
your IP address.
Flashing (three flashes)
Indicates an Ethernet DNS Lookup error. Make sure you
have an Internet connection that has access to the
world wide web.
Tab.
11.10:
Ethernet LED descriptions
SYSTEM TROUBLE Flashing (two flashes) - Cellular Trouble
Heartbeat
LED
RX LED
Plug-in Status LED
Function
On Steady
Flashing (one flash)
N/A
Indicates the plug-in
module is missing.
Verify the plug-in
module is firmly
inserted into the
module connector.
On Steady
Flashing (two flashes)
Off
Indicates the plug-in
module is not
recognized. Verify the
correct plug-in
module is firmly
inserted into the
module connector.
Verify the latest
firmware is installed
to support the
module you have.
Summary of Contents for B465
Page 1: ...Conettix Universal Dual Path Communicator B465 en Installation and Operation Manual ...
Page 2: ......
Page 114: ......