86
en | Maintenance and troubleshooting
Conettix Universal Dual Path Communicator
2017.11 | 05 | F.01U.311.207
Installation and Operation Manual
Bosch Security Systems, Inc.
Flash pattern
Function
Off
Is in an off state during the power up sequence.
Tab.
11.12:
POWER LED descriptions
BATTERY LED
Flash pattern
Function
Off
Indicates normal operations.
Flashing (one flash)
Indicates low battery voltage.
Flashing (two flashes)
Indicates a missing battery (below 12.1 V).
Flashing (three flashes)
Indicates a bad battery (low for 72 hours). Replace the
battery with a new one.
Flashing (four flashes)
Indicates a battery charger failure. Failure can only be
cleared by powering down the module and rebooting. If
the problem continues the module will require a board
replacement.
Tab.
11.13:
BATTERY LED descriptions
11.2
B46 LED status and sounder
Refer to the following table for LED status indicators.
SYSTEM TROUBLE LED patterns
Flash pattern
Function
Off
Indicates normal operations.
Flashing
Indicates Ethernet communication errors. Refer to
SYSTEM TROUBLE Flashing (one flash) - Ethernet table
for more information.
Flashing
Indicates cellular communication errors. Refer to
SYSTEM TROUBLE Flashing (two flashes) - Cellular
table for more information.