Conettix Universal Dual Path Communicator
Specifications and certifications | en
111
Bosch Security Systems, Inc.
Installation and Operation Manual
2017.11 | 05 | F.01U.311.207
Contact ID report
(i = input number, 001-004)
(t = trouble type)
B465 Event
B465 Event #
1-330-99-000
SYSTEM PERIPHERAL TROUBLE
When the B465 detects any of the fault
conditions below it creates a generic trouble
event and sends a SYSTEM PERIPHERAL
TROUBLE report.
–
Ethernet cable open
–
Ethernet IP address error
–
Plug-in cellular module not recognized
–
Plug-in cellular module, modem failed
–
Plug-in cellular module, SIM card
missing
–
Plug-in cellular module, SIM PIN wrong
–
Plug-in cellular module, SIM PIN locked
out
–
Plug-in cellular module, SIM PIN not
needed
–
Cellular, configuration incorrect
–
Cellular, not registered for Bosch
Cellular Service
–
Cellular, invalid access point
–
Cellular IP address incorrect
–
Cellular, low signal
–
Cellular, one or no cellular towers
detected
28
3-330-99-000
SYSTEM PERIPHERAL TROUBLE
(restoral)
When the B465 detects all of the fault
conditions above are cleared, it creates a
generic trouble restoral event and sends a
SYSTEM PERIPHERAL TROUBLE Restoral
report.
29
1-333-99-000
EXPANSION MODULE FAILURE
When the B465 detects a cellular plug-in
module is not plugged in, it creates a plug-in
module missing event and sends an
EXPANSION MODULE FAILURE report.
33
3-333-99-000
EXPANSION MODULE FAILURE
(restoral)
When the B465 detects a cellular plug-in
module after a plug-in module failure event,
it creates a plug-in module restoral event
and sends an EXPANSION MODULE FAILURE
Restoral report.
34
Summary of Contents for B465
Page 1: ...Conettix Universal Dual Path Communicator B465 en Installation and Operation Manual ...
Page 2: ......