en | Specifications and certifications
Conettix Universal Dual Path Communicator
2017.11 | 05 | F.01U.311.207
Installation and Operation Manual
Bosch Security Systems, Inc.
12.3
B465 Event/Report Table
The B465 monitors the status of the primary power source, battery, and communication to the
primary receiver and secondary receivers. The B465 sends the status in Contact ID reports as
shown in the table below.
Contact ID report
(i = input number, 001-004)
(t = trouble type)
B465 Event
B465 Event #
1-110-99-iii
FIRE
When a B465 input that is configured for Fire
Alarm is shorted, the B465 makes a Panel
Fire Alarm event and sends a FIRE report.
7
3-110-99-iii
FIRE (restoral)
When a B465 input that is configured for Fire
Alarm returns to normal after being shorted,
the B465 makes a Panel Fire Alarm Restoral
event and sends a, FIRE restoral report.
8
1-130-99-iii
BURGLARY
When a B465 input that is configured for
Burglary Alarm is shorted, the B465 makes a
Panel Burglary Alarm event and sends a
BURGLARY report.
13
3-130-99-iii
BURGLARY (restoral)
When a B465 input that is configured for
Burglary Alarm returns to normal after being
shorted, the B465 makes a Panel BURGLARY
Alarm Restoral event and sends a BURGLARY
restoral report.
14
1-137-99-000
TAMPER
The B465 sends TAMPER reports for faults
on the tamper circuit. When an enclosure
tamper switch is connected to the B465
tamper circuit (TMPR connector), opening
the enclosure door is a fault.
21
3-137-000
TAMPER (restoral)
The B465 sends TAMPER restoral reports
when the tamper circuit returns to normal
after a fault. When an enclosure tamper
switch is connected to the B465 tamper
circuit (TMPR connector), closing the
enclosure door returns the tamper circuit to
normal.
22
1-200-99-iii
FIRE SUPERVISORY
When a B465 input that is configured for Fire
Supervisory is shorted, the B465 makes a
Panel Fire Supervisory event and sends a
FIRE SUPERVISORY report.
7
3-200-99-iii
FIRE SUPERVISORY (restoral)
When a B465 input that is configured for Fire
Supervisory returns to normal after being
shorted, the B465 creates a Panel Fire
Supervisory Restoral event and sends a, FIRE
FIRE SUPERVISORY Restoral report.
8