Conettix Universal Dual Path Communicator
Installation | en
31
Bosch Security Systems, Inc.
Installation and Operation Manual
2017.11 | 05 | F.01U.311.207
1
3
2
5
TMPR
BAT
ETHERNET
EXTERNAL
ANNUNC
X
MODULE 1
Y
MODULE
RELEASE
1 COM 2
PNL LINE 2
3 COM 4
PNL LINE 1
C NO
RELAY 2
18VAC
NO C NC
RELAY 1
TRBL
TX
RX
AC
PANEL
LINE 2
USB
ETHERNET
100BASE-T
LINK
COMMUNICATION MODULE 1
3 COM 4
1 COM 2
R Y G
B
SDI2
Device Bus
BATTERY
PANEL
LINE 1
BATTERY
AC
RX
TX
SYSTEM TROUBLE
INPUTS
2.2 k End of
Line Resistors
C NO
RELAY 3
12V
AUX COM
4
6
3
24 VDC
or
16.5 VAC
+
-
BATTERY
Figure
4.12: NON-power limited wiring for a wired transformer
Callout
ー
Description
1
ー
Conduit required for use with external batteries
2
ー
Battery terminals. is non-power limited
3
ー
D1640-120WI UL Listed Class 2 Wired Transformer 16.5 VAC, 40 VA, 60 Hz (tuck the
wires behind the battery to ensure the proper clearance)
4
ー
12 VDC sealed lead-acid rechargeable battery (D126/D1218)
5
ー
Battery wires (red and black)
6
ー
B465 ground wire connection (tuck the wires behind the battery to ensure the proper
clearance)
Battery maintenance
Use sealed lead-acid rechargeable battery (12.0 VDC, 7 Ah to 12.0 VDC, 18 Ah). The B465
supports up to 18 Ah of battery. Replace the batteries every 3 to 5 years.
Record the date of installation directly on the battery.
!
Caution!
Exceeding the maximum output ratings or installing the transformer in an outlet that is
routinely switched off causes heavy discharges. Routine heavy discharges can lead to
premature battery failure.