88
en | Maintenance and troubleshooting
Conettix Universal Dual Path Communicator
2017.11 | 05 | F.01U.311.207
Installation and Operation Manual
Bosch Security Systems, Inc.
Flash pattern
Function
Flashing (two flashes)
Indicates a missing battery (below 12.1 V).
Flashing (three flashes)
Indicates a bad battery (low for 72 hours). Replace the
battery with a new one.
Flashing (four flashes)
Indicates a battery charger failure. Failure can only be
cleared by powering down the module and rebooting. If
the problem continues the module will require a board
replacement.
Tab.
11.16:
BATTERY LED descriptions
B46 sounder conditions
The B46 external annunciator uses a built-in audio sounder to produce an audio signal
indicating to the user if there is a problem that needs user attention specific to the B465.
Condition
Sounder response
Low or missing Input
power on the B465
module
The sounder emits an audio tone for once every ten seconds
when the B465 module programming
for Input Power Supervision
is enabled. This pattern is repeated until the Input power issue is
restored.
Low or missing battery
voltage on the B465
module
The sounder emits an audio tone for once every ten seconds
when the B465 module programming
for Battery Supervision
is
enabled. This pattern is repeated until the battery power issue is
restored.
Configuration errors
The sounder emits a double “beep” audio tone every 4 seconds
when a configuration error is detected. The pattern is repeated
until the configuration issue is resolved.
Firmware or hardware
issues
The sounder emits a steady audio tone when there is a firmware
or hardware issue with the B465. This pattern remains on steady
until the issue is resolved.
Table
11.17: B46 Sounder conditions
11.3
Show the firmware version
To show the firmware version using an LED flash pattern:
–
If the optional tamper switch is installed:
–
With the enclosure door open, activate the tamper switch.
–
If the optional tamper switch is NOT installed:
–
Momentarily short the tamper pins.
When the tamper switch is activated (open to closed), the heartbeat LED stays Off for 3 sec
before indicating the firmware version. The LED pulses the major, minor, and micro digits of
the firmware version, with a 1 sec pause after each digit. The following is an example: The
version 1.4.3 would show as LED flashes: [3 second pause] *__****__*** [3 second pause, then
normal operation].