Conettix Universal Dual Path Communicator
Specifications and certifications | en
99
Bosch Security Systems, Inc.
Installation and Operation Manual
2017.11 | 05 | F.01U.311.207
12.1.4
24 VDC Input power requirements
24 VDC applied to power supply input terminals
B
C
Standby Power On Normal
Current (mA)
Alarm Current (mA)
Model Number
Qty Used Each
Unit
Qty
Total
Each Unit Qty
Total
B465
1
120
x 1
= 120
160
x 1
= 160
B46
______
23
x 1
= ____
23
x 1
= ____
B450
B208
B308
B440
______
35
x 1
= ____
150
x 1
= ____
B441
______
35
x 1
= ____
150
x 1
= ____
B442
______
35
x 1
= ____
150
x 1
= ____
B443
______
35
x 1
= ____
150
x 1
= ____
B444
______
35
x 1
= ____
150
x 1
= ____
Aux Power
(0 - 500 mA
______
_____
x Qty
= ______
______
x Qty
= ______
____
______
_____
x Qty
= ______
______
x Qty
= ______
____
______
_____
x Qty
= ______
______
x Qty
= ______
Total B = ____
Total C = ____
Tab.
12.20:
Current rating chart for standby calculations
Notice!
Maximum power supply current for Total B in the table above is 675 mA, and the maximum
power supply current for Total C is 830 mA.