Notice!
NFPA Fire Application Note
Cellular sole path communications with supplementary Ethernet communications
When cellular communications are configured under NFPA 72 (2010 - 2016) requirements for
a single communication technology, Ethernet can be used as a supplementary communication
path without requiring the secondary power capacity requirements on the protected premises
network equipment, where acceptable to the authority having jurisdiction. This makes it
possible for fire signals to be transmitted over Ethernet to the central monitoring station
when cellular communications are disrupted.
To enable encryption for IP network communications, refer to the AES Encryption parameters
in
.
5.4
Compatible central station receivers
Sending Conettix IP reports requires a Bosch central station receiver. The following receivers
are compatible with B465:
–
Conettix D6600 Communications Receiver/Gateway
–
Conettix D6100IPv6 Communications Receiver/Gateway
–
Conettix D6100i Communications Receiver/Gateway
Central Station information
Perform the following:
1.
Verify the receiver is configured in NNC mode.
2.
Select Integrated Device as the Network Device for the B465.
3.
Enter the same NNC number that the B465 creates from the Account Number / NNC
parameter.
4.
Select the same supervision times as selected in the B465 Ethernet Supervision Time and
Cellular Supervision Time parameters.