Conettix Universal Dual Path Communicator
Specifications and certifications | en
113
Bosch Security Systems, Inc.
Installation and Operation Manual
2017.11 | 05 | F.01U.311.207
Contact ID report
(i = input number, 001-004)
(t = trouble type)
B465 Event
B465 Event #
1-373-99-iii
FIRE TROUBLE
When a B465 input that is configured for Fire
Trouble is shorted, the B465 makes a Panel
Fire Trouble event and sends a FIRE
TROUBLE report.
9
3-373-99-iii
FIRE TROUBLE (restoral)
When a B465 input that is configured for Fire
Trouble returns to normal after being
shorted, the B465 makes a Panel Fire
Trouble Restoral event and sends a, FIRE
TROUBLE Restoral report.
10
1-380-99-iii
BURGLARY TROUBLE
When a B465 input that is configured for
Burglary Trouble is shorted, the B465 makes
a Panel Burglary Trouble event and sends a
BURGLARY TROUBLE report.
9
3-380-99-iii
BURGLARY TROUBLE (restoral)
When a B465 input that is configured for
Burglary Trouble returns to normal after
being shorted, the B465 makes a Panel
Burglary Trouble Restoral event and sends a,
BURGLARY TROUBLE Restoral report.
10
1-602-99-000
PERIODIC TEST
When the B465 is configured to send test
reports it sends a PERIODIC TEST report.
36
1-608-99-000
PERIODIC TEST (system trouble
present)
When the B465 is configured to send test
reports and there is a module or input fault
it sends a PERIODIC TEST (system trouble
present) report.
37