en | Specifications and certifications
Conettix Universal Dual Path Communicator
2017.11 | 05 | F.01U.311.207
Installation and Operation Manual
Bosch Security Systems, Inc.
12.1.5
Required programming to meet UL 864
This section identifies the programming requirements for UL 864 Commercial Fire
applications.
Notice!
TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED
PARTIES
This product incorporates field-programmable software. In order for the product to comply
with the requirements in the Standard for Control Units and Accessories for Fire Alarm
Systems, UL 864, you must limit certain programming features or options to specific values.
Parameter
Permitted in UL
864?
(Yes/No)
Possible settings
Settings permitted
in UL 864
(set to AC)
Yes
AC, DC
AC - when using
transformer as
source.
Primary Power Fail Delay,
page 73
Yes
0 to 255 minutes 60 to 180 minutes
Primary Power Fail sends
reports, page 73
Yes
Enabled/Disabled Enabled - if sending
report from B465,
disabled if using
relay outputs to
control panel
(set to DC)
Yes
AC/DC
DC - when powering
from UL listed
control panel or
power supply
Primary Power Fail Delay,
page 73
Yes
0 to 255 minutes 0 to 3 minutes
Primary Power Fail sends
reports, page 73
Yes
Enabled/Disabled Enabled - if sending
report from B465,
disabled if using
relay outputs to
control panel
Yes
Enabled/Disabled Enabled
Battery faults send
reports, page 74
Yes
Enabled/Disabled Enabled - if sending
report from B465,
disabled if using
relay outputs to
control panel