StarLink
™
SLE Commercial LTEVI & LTEAI Series Dual-Path Alarm Communicators -- Installation Instructions
1
ADDITIONAL COMPONENTS
In addition to the models listed above, the following sub-
assemblies are available:
SLE-ULPS-R
- Power Supply. Required for installations
where the control panel cannot provide the Auxiliary
power required to operate the StarLink communicator.
Uses a standard 4AH / 12V minimum (7AH maximum,
required with optional Wi-Fi Module) rechargeable bat-
tery to provide communicator standby power. Requires
connection to either the model NAPCO TRF12/T123
(16.5V / 20VA) external plug-in transformer or the chas-
sis-mounted 16.5VAC / 20VA transformer affixed inside
the housing (see wiring diagrams further in this manual).
Note:
For models without the SLE-ULPS-R, connect
the communicator terminals 1 and 2 to the control panel
Aux Power terminals (observing polarity).
SLE-WIFI-MODULE
- Allows your Napco StarLink
™
device
to connect to the Internet by means of a wireless (Wi-Fi)
link, eliminating a wired Ethernet cable connection.
Note:
7AH battery required when using the
SLE-
WIFI-MODULE
. For more information, see WI2191.
SLE-DLCBL
- Download Cable, 6 feet
SLE-ANTEXT30
- Extended antenna with 30 feet of cable
SLE-ANTEXT50
- Extended antenna with 50 feet of cable
SLE-ANTEXT75
- Extended antenna with 75 feet of cable
SLE-ANTEXT100
- Extended antenna with 100 feet of cable
(Any suitable external cellular antenna is permitted by
UL). Always follow the manufacturer's installation in-
structions.
Note:
Antennas are not Listed by UL.
GEM-Tamperkit
- Tamper switches and screws to protect
metal housing (see page 14).
SPECIFICATIONS
The following specifications apply to all StarLink communi-
cator models unless otherwise stated:
Electrical Ratings for 120VAC, 60Hz
For Models with Power Supply
Input Voltage: 120VAC nominal
Input Current: 200mA maximum
Maximum Charging Current: 200mA
StarLink™ SLE Commercial
LTEVI & LTEAI Series
Dual-Path Alarm Communicators
INSTALLATION INSTRUCTIONS
WI2327E.aLF 11/20
R
333 Bayview Avenue, Amityville, New York 11701
For Sales and Repairs, (800) 645-9445
For Technical Service, (800) 645-9440 or visit us at
http://tech.napcosecurity.com/
(Note: Technical Service is for security professionals only)
Publicly traded on NASDAQ Symbol: NSSC
© NAPCO 2020
INTRODUCTION
The StarLink
™
LTE Series Dual-Path Commercial / Resi-
dential Fire alarm capture IP communicators are fully su-
pervised, wireless digital two-way subscriber units. All
models are compatible with most 12/24VDC alarm control
panels (always adhere to the documentation provided by
the control panel manufacturer). These communicators are
for use as the primary means of communication with the
central station and do not have backup mode capability.
No POTS (Telco Line) connection permitted. Dual Path
Communicators can also be utilized as a Sole Path Cell
Communicator.
See WI2140 for programming information.
The following models are available:
SLE-LTEVI-CFBPS & SLE-LTEAI-CFBPS
: Commercial /
Residential Fire LTE TCP/IP Communicators in red met-
al housing with SLE-ULPS-R power supply and 16.5V /
20VA transformer mounted inside housing
SLE-LTEVI-CFB & SLE-LTEAI-CFB
: Commercial / Resi-
dential Fire LTE TCP/IP Communicators in red metal
housing. Powered directly from control panel
Aux/Remote Fire Power (no power supply, no trans-
former, rated nominal 12/24VDC input)
The following features are included with models that in-
clude a SLE-ULPS-R power supply:
Power limited output to the StarLink communicator PC
board 12V input terminals
Battery connection red and black flying leads
Monitored battery charging and Active battery test circuits
StarLink communicator trouble input (from StarLink PC
board
PGM1
terminal to detect StarLink communicator
trouble)
Requires a sealed lead acid min 4AH / max 7AH battery
for minimum 24-hour standby time (max charge current
200mA).
Trouble relay output (
C
,
N/O
and
N/C
terminals) to
wire to a panel zone dedicated to "Communicator Trou-
ble" (dry contacts). Remove jumper "
J2
" isolate relay
OUT1 common from ground
Green
AC ON
LED visible from the exterior housing
Yellow
TROUBLE
LED "
D4
" on PC board. Flashes sig-
nify:
One flash: AC fail / brownout
Two flashes: Low battery
Three flashes: Charging circuit trouble
Four flashes: StarLink communicator trouble
The housing-mounted transformer (when provided) is
mounted inside its own housing compartment with a re-
placeable UL Listed .5A fast blow primary fuse. 120VAC
connections are to be made by a licensed electrician using
suitable connectors, in accordance with N.E.C. and local
code requirements.
AGENCY LISTINGS
UL 864 Standard For Control Units and Accessories For Fire
Alarm Systems, 10th Edition
UL 1610 Standard For Central-Station Burglar-Alarm Units
UL 985 Standard For Household Fire Warning System Units
UL 1023 Standard For Household Burglar-Alarm System Units
UL 1076 APOU Proprietary Alarm Systems
UL 365 APAW Police Connect
NYC Fire Dept. Certificate of Approval #6317 & 6318