background image

StarLink

 SLE Commercial LTEVI & LTEAI Series Dual-Path Alarm Communicators -- Installation Instructions 

optionally  have  front  and  rear  tamper  switches  installed 

(GEM-Tamperkit)  and  wired  to  the  control  panel  (see 

page 14).  

Note:

  The tamper switch on the communicator 

PC  board  is  not  used  in  this  housing  (but  continues  to 

function if pressed).    

 

NYC Fire Department Requirements  

 

1.  All uses, configurations, arrangements and functions, ap-

plications  and  installations  shall  comply  with  the  provi-

sions  of  New  York  City  Construction  Codes,  specifically 

Building  Code  Chapter  9  &  1RCNY  §3616-04.    Further, 

the installation shall be in accordance with applicable pro-

visions of New York City Fire Code, New York City Electri-

cal  Code,  manufacturer's  installation  requirements,  and 

UL Standard 864. 

2.  When used Dual Path LTE Communicator (IP and Cellu-

lar)  for  Central  Station  communication  both  primary  and 

secondary  channels  of  communication  shall  be  required 

and shall meet the conditions of 4.1 – 4.7.  IP communica-

tion  shall  be  used  as  primary  channel  of  communication 

with  Central  Station  and  Cellular  Communicator  shall  be 

used  as  the  secondary  channel  of  communication  or  in 

reverse  order:    Cellular  Communicator  as  primary  and 

Internet connection as the secondary channel. 

a.  Each  communication  channel  shall  be  monitored  for 

integrity at intervals not exceeding 24 hours. 

b.  Failure any channel of communication shall be annun-

ciated  at  the  protected  premises  within  5  minutes  of 

failure. 

c.  When any channel of communication has failed, a trou-

ble  signal  shall  be  sent  to  Central  Station  within  5 

minutes of failure by the remained active channel. 

d.  Reliability of the signal shall be achieved by any of the 

following: 

 

Signal repetition - multiple transmissions repeating the 

same signal 

 

Parity check - a mathematically check sum algorithm 

of a digital message that verifies correlation between 

transmitted and received message 

 

An  equivalent  means  that  provides  a  certainty  of 

99.99  percent  that  the  received  message  is  identical 

the zone as indicated in the wiring diagrams further in this 

manual.   

  For  models 

with 

the 

SLE-ULPS-R 

Power  Supply,  wire 

this Power Supply trouble output relay to the two terminals 

of  the  control  panel  zone  dedicated  to  the  trouble.    With 

the  GEMC  Commercial  Fire  control  panels,  use  the  dry 

contacts of the Power Supply relay by removing the jump-

er  and  using  the  contacts  of  the  Power  Supply  relay 

(Common and N/O) in series with a 2.2k EOLR.   

  For communicator models 

without 

the 

SLE-ULPS-R 

Pow-

er Supply (powered by the control panel Aux Power termi-

nals),  wire  the  communicator  directly  to  the  12V  of  the 

control  panel.    Program  the  communicator  to  report  all 

troubles on 

OUT1

Common 

and 

N/C

.   

  You can also wire across the dedicated zone on a GEMC-

EZM8.    Thus  when  a  communicator  trouble  is  detected, 

the communicator 

OUT1 

activates the control panel zone, 

and the panel generates a local annunciation.   

  Optionally, you may also wire the FACP Trouble Relay to 

IN2

Common 

and 

N/O

 terminals in parallel with a 10k 

EOLR.  With Gemini C-Series (GEMC) control panels, we 

recommend  using  the  Fire  Aux  Relay.    Program  the  Fire 

Aux Relay to activate as a trouble relay.  Wire this relay to 

the StarLink module 

IN2 

terminal; by wiring the EOLR  in 

parallel with the 

Common 

and 

N/O

 of the 

OUT1

 relay.   

 

 

Note: 

 We  recommend using  the  text  "Communicator 

Trouble" as the Zone Description. 

 

StarLink Communicator Supervision  

  If  the  two  Telco  wires  (DACT  interconnect  wiring  to  the 

communicator)  between  the  StarLink  communicator  and 

the  control  panel  are  cut  or  otherwise  disconnected,  the 

control  panel  must  detect  and  generate  a  local  trouble 

indication.  Program the control panel for telephone super-

vision.    Program  the  StarLink  communicator  using  the 

Management  Center 

Advanced  Features

  screen  (at 

www.NapcoNOC.com

)  to  enable 

Tip/Ring  Wiring  Fault 

Report

.  Refer to wiring diagram. 

 

Supervision Time Schedule Considerations 

  If a status change (alarm trouble, etc.) is transmitted, the 

communicator supervision timer is restarted.   

  For  example,  if  a  status  change  is  sent,  the  next  regular 

supervision  transmission  will  occur  at  the  interval  deter-

mined by your rate plan.   

 

Configuration Download / Firmware Updates 

  Technician on site required. 

  For Commercial Installations a technician is required to be 

on site during any reprogramming of the communicator or 

control  panel  and  must  perform  /  re-perform  acceptance 

testing.  To perform a download or update the communi-

cator firmware, jumper 1 must be  removed.  UL requires 

that  the  jumper  be  replaced  after  the  download  is  com-

plete.  

Failure  to  replace  the  jumper  would  allow  down-

loads  to  the  communicator  without  a  technician  on-

site

.   

 

  For Residential installations jumper 1 may be removed to 

permit uploading and downloading without a technician on 

site,  however,  the  dealer  is  responsible  for  ensuring  the 

system  is  operating  correctly  after  any  downloads  or 

changes to the system. 

 

Cover Tamper 

  The SLE series communicators in the metal housings may 

10-1/8" 

11-1/2" 

9-1/2" 

9-21/64" 

Red and White Metal Housing Dimensions (inches) 

Summary of Contents for SLE-LTEAI-CFB

Page 1: ...icators are fully su pervised wireless digital two way subscriber units All models are compatible with most 12 24VDC alarm control panels always adhere to the documentation provided by the control panel manufacturer These communicators are for use as the primary means of communication with the central station and do not have backup mode capability No POTS Telco Line connection permitted Dual Path ...

Page 2: ...igh input for wiring to the control panel bell output When this input detects a pulsing temporal 3 high it sends a Fire alarm a pulsing temporal 4 CO Alarm a CO alarm is sent When used these conductors must be run in conduit max 20 feet for Commercial Fire and 3 feet for Residential Fire For this input to re port to a central station the StarLink communicator must be configured with the central st...

Page 3: ...T2 Common Dry contact Form C relay Relay rated 30V AC DC 500mA TB24 N C OUT2 Normally closed Dry contact Form C relay LED DESCRIPTIONS The PC board contains several LED s as follows GREEN RF SIGNAL STRENGTH LED Labeled D3 this LED is located at the lower right corner of the PC board Every 30 seconds the StarLink communicator receiver section turns on and listens to the cell tower Depending on the ...

Page 4: ...ces for 24 hours unless an engine driven genera tor is provided on the premises then only 4 hours of UPS backup are required JUMPER DESCRIPTIONS Jumper block labeled X5 from top to bottom as detailed in the table below Note Contact ID is always available in response to a Contact ID handshake The SLE Series Dual Path communicators are compatible with 4 2 Pulse Dialing formats with 10pps 20pps and 4...

Page 5: ...unt and register specific StarLink com municator modules at www NapcoComNet com Accounts and modules registered via the Internet are enabled for activation within 24 hours STEP 2 SELECT A MOUNTING LOCATION The mounting location should be indoors within the protect ed area and selected based on RF performance It is HIGHLY recommended that the installer carefully adhere to the following recommendati...

Page 6: ...vate the trouble with an open by wiring the EOLR in series with the Common and N C of the OUT1 relay Activate the trouble with a short by wiring the EOLR in parallel with the Common and N O of the OUT1 relay The communicator must also report this trouble to the central station With NAPCO GEMC control panels wire SIGNALS ORIGINATED AT THE NOC NOC Originated Alarms Contact ID Event Data Sent Initiat...

Page 7: ...and N O in series with a 2 2k EOLR For communicator models without the SLE ULPS R Pow er Supply powered by the control panel Aux Power termi nals wire the communicator directly to the 12V of the control panel Program the communicator to report all troubles on OUT1 Common and N C You can also wire across the dedicated zone on a GEMC EZM8 Thus when a communicator trouble is detected the communicator...

Page 8: ...es with which the compatibility has been determined by UL Listing Report 5 Only enclosures painted red in color shall be used 6 Underwriters Laboratories Inc s listing requirements and limitations shall be complied with to the transmitted message e The maximum duration between the initiation of an alarm signal at the protected premises transmission of the signal and subsequent display and recordin...

Page 9: ...e transformer compartment from the yellow secondary wires of the transformer Remove shunt J2 to isolate relay OUT1 common from ground i e jumper on wet circuit common off dry contact When wet configuration is used the power should be derived from the alarm control panel J7 Remove shunt to disable 10K EOLR across pins 1 and 8 of primary TELCO input Do not remove if Tip Ring Wiring Fault Report is e...

Page 10: ...vision Requires all 8 wires in the RJ 45 cable JP1 Shunt JP1 on bottom 2 pins when using the SLE ULPS R Shunt on top 2 pins when NOT using the SLE ULPS R These connections only used without Power Supply EOLR JP2 Remove shunt on JP2 to enable TELCO 2 trouble Not required if JP2 shunt is removed and FACP monitors TELCO 2 To FACP Zone Dedicated to Radio Trouble When using JP2 option monitoring Telco ...

Page 11: ... when not using the SLE ULPS R RJ31X RING TIP GREEN RED GREEN RED WIRE DIRECTLY TO CONTROL PANEL USE FOR SHORTER DISTANCES OPTIONAL WIRE TO RJ31X USE FOR LONGER DISTANCES RJ31X RING TIP GREEN RED WIRE DIRECTLY TO CONTROL PANEL USE FOR SHORTER DISTANCES OPTIONAL WIRE TO RJ31X USE FOR LONGER DISTANCES GREEN The feature Tip Ring Wiring Fault Report is required for supervision RED JP2 Remove shunt on ...

Page 12: ...removed and FACP monitors TELCO 2 Program only TELCO 1 supervision Note Connect IN2 to a panel output used for identifying Telco line cut this is the DACT interconnect wiring to the radio PC Board All connections are power limited except AC Mains and battery terminals Or use a 12V 24V UL Listed monitored power supply 10kΩ 10kΩ 10kΩ EOLR Requires all 8 wires in the RJ 45 cable JP1 Shunt JP1 on top ...

Page 13: ...or supervision and central station reporting through the StarLink SLE LTEVI FIRE radio By removing the JP2 shunt and enabling the feature Tip Ring Wiring Fault Report when any radio trouble is detected the StarLink radio will remove voltage from the secondary telephone output triggering the FACP to locally annunciate the Telco trouble and report the trouble to the central station Note Some FACPs r...

Page 14: ...r that opening the enclosure door will cause a tamper alarm Wiring a normally closed sensor loop for tamper supervision wire to a zone on the control panel GEM Tamperkit consists of Description QTY SC206LF Slotted Pan Head 6 32 x 3 4 Machine Screw 6 SW105 Tamper Switch 2 Tamper Switch Mounting Instructions Back Tamper Door Tamper VIEW OF TAMPER SWITCHES 1 ENCLOSURE BASE 2 BACK TAMPER SWITCH TO PRE...

Page 15: ... TRF12 T123 TRANSFORMER FOR CONNECTION TO SLE CHARGER BOARD UL LISTED SURFACE OR FLUSH MOUNT OUTLET BOX AND NON SWITCHED RECEPTACLE WALL TRANSFORMER SECONDARY WIRING CONDUIT LIMITED TO 20 FEET MAXIMUM LENGTH Maintain a minimum of 1 4 inch separation of circuits transformer secondary wiring from 120V branch circuit EXAMPLE OF CONDUIT LOCATION Optional Alternate Methods for Commercial Fire Branch Ci...

Page 16: ...may not be compromised or circumvented or that the product or system will prevent any personal injury or property loss by burglary robbery fire or otherwise nor that the product or system will in all cases provide adequate warning or protection A properly installed and maintained alarm may only reduce risk of burglary robbery fire or otherwise but it is not insurance or a guarantee that these even...

Reviews: