Alternate Telco Line to Alarm Panel Supervision
The following wiring and programming method allows an existing FACP to use its two telephone connections
(primary and secondary) for supervision and central station reporting through the StarLink SLE-LTEVI-FIRE radio.
By removing the
JP2
shunt and enabling the feature "
Tip/Ring Wiring Fault Report
", when any radio trouble is
detected, the StarLink radio will remove voltage from the secondary telephone output, triggering the FACP to
locally annunciate the Telco trouble and report the trouble to the central station.
Note:
Some FACPs require
J7
shunt to be removed for Primary Phone line to restore correctly.