3500/42 Operation and Maintenance
Configuration Information
23
OK Limits
Transducer
Upper
Lower
Center Gap Voltage
Without
Barriers
(V)
With
Barriers
(V)
Without
Barriers
(V)
With
Barriers
(V)
Without
Barriers
(V)
With
Barriers
(V)
3300 8 mm
3300 5 mm
7200 5 mm
7200 8 mm
-16.75
-16.75
-2.75
-2.75
-9.75
-9.75
7200 11 mm
-19.65
*
-3.55
*
-11.6
*
7200 14 mm
-16.75
*
-2.75
*
-9.75
*
3000 (-18V)
-12.05
*
-2.45
*
-7.25
*
3000 (-24V)
-15.75
*
-3.25
*
-9.5
*
3300 RAM
-12.55
-12.15
-2.45
-2.45
-7.5
-7.3
3300 16 mm
HTPS
-16.75
*
-2.75
*
-9.75
*
* Barriers are not supported with this transducer option.
Note: With Barriers includes BNC Internal Barrier I/O Modules.
Transducer Jumper Status (on I/O Module)
Returns the position of the Transducer Jumper on the Proximitor/Seismic I/O
Module. Refer to Section 4.1(Setting the I/O Jumper)for the function of this
jumper.
Alarm Mode
Latching
Once an alarm is active it will remain active even after the proportional value
drops below the configured setpoint level. The channel will remain in alarm
until it is reset using one of the following methods:
- the reset switch on the front of the Rack Interface Module
- the contact on the Rack Interface I/O Module
- the Reset button in the Operator Display Software
- the reset command through the Communication Gateway Module
- the reset command through the Display Interface Module
- the reset command in the Rack Configuration Software
Nonlatching
When an alarm is active it will go inactive as soon as the proportional value
drops below the configured setpoint level.
Alert should be the first level alarm that occurs when the transducer signal
level exceeds the selected value. Danger should be the second level alarm
that occurs when the transducer signal level exceeds the selected value.
The Alert and Danger values are set on the Setpoint screen.