Configuration Information
3500/42 Operation and Maintenance
22
Customize button
Used to adjust the Scale Factor for transducers. If Non-standard is selected as
the transducer type, the OK Limits can also be adjusted. The Non-standard
transducer's scale factor must be between 85 and 230 mV/mil. Also, there must
be at least 2 volts between the Upper and Lower OK Limits.
Transducer
Scale Factor
Without
Barriers
With Bently
Nevada Internal
Barriers
Standard I/O
With
Barriers
Discrete TMR
I/O With
Barriers
Bussed TMR
I/O With
Barriers
3300 5 and 8 mm
7200 5 and 8 mm
200 mV/mil
200 mV/mil
192 mV/mil
200 mV/mil
199 mV/mil
7200 11 mm
100 mV/mil
*
*
*
*
7200 14 mm
100 mV/mil
*
*
*
*
3000 (-18V)
200 mV/mil
*
*
*
*
3000 (-24V)
285 mV/mil
*
*
*
*
3300 RAM
200 mV/mil
200 mV/mil
192 mV/mil
200 mV/mil
199 mV/mil
3300 16 mm HTPS
100 mV/mil
*
*
*
*
Note: ±15 % scale factor adjustment allowed.
* Barriers are not supported with this transducer option.