Configuration Information
3500/42 Operation and Maintenance
38
Customize button
Used to adjust the Scale Factor of transducers. If Non-standard is selected as
the transducer type, the OK Limits can also be adjusted. The Non-standard
transducer's scale factor must be between 8.5 and 23 mV/mil. Also, there must
be at least 2 volts between the Upper and Lower OK Limits.
Scale Factor
Transducer
Without Barriers
25 mm
20 mV/mil
35 mm
20 mV/mil
50 mm
10 mV/mil
Note: ±15 % scale factor adjustment allowed.
OK Limits
Transducer
Upper (V)
Lower (V)
Center Gap Voltage
(V)
25mm
-12.55
-1.35
-6.95
35mm
-12.55
-1.35
-6.95
50mm
-12.55
-1.35
-6.95