Configuration Information
3500/42 Operation and Maintenance
30
The following transducer types are available for the Thrust Position Channel
(barrier I/O module):
3300 - 5mm Proximitor
3300 - 8mm Proximitor
7200 - 5mm Proximitor
7200 - 8mm Proximitor
3300 RAM Proximitor
Nonstandard
Customize button
Used to adjust the Scale Factor for transducers. If Non-standard is selected as
the transducer type, the OK Limits can also be adjusted. The Non-standard
transducer's scale factor must be between 85 and 230 mV/mil. Also, there must
be at least 2 volts between the Upper and Lower OK Limits.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com