Maintenance
3500/42 Operation and Maintenance
134
13. If you can not verify any configured OK limit, go to Section 5.1.11 (If a
Channel Fails a Verification Test).
14. Disconnect the test equipment and reconnect the PWR, COM, and SIG field
wiring to the channel terminals on the Monitor I/O Module. Press the RESET
switch on the Rack Interface Module (RIM) and verify that the OK LED comes
on and the OK relay energizes.
15. Repeat steps 1 through 14 for all configured channels.
16. Return the bypass switch for all configured channels to their original setting.
Thrust Position Default OK Limits Table
Transducer
Lower OK Limit
(volts)
Upper OK Limit
(volts)
7200 5 & 8 mm w/ barriers
-1.05 to -1.15
-1.23 to -1.33 *
-18.15 to -18.25
7200 5 & 8 mm w/o barriers
-1.23 to -1.33
-18.99 to -19.09
7200 11 mm w/o barriers
-3.50 to -3.60
-20.34 to -20.44
7200 14 mm w/o barriers
-1.6 to -1.7
-18.0 to -18.1
3300 5&8 mm w/ barriers
-1.05 to -1.15
-1.23 to -1.33 *
-18.15 to -18.25
3300 5&8 mm w/o barriers
-1.23 to -1.33
-18.99 to -19.09
3000 (-18V) w/o barriers
-1.11 to -1.21
-13.09 to -13.19
3000 (-24V) w/o barriers
-2.2 to -2.3
-16.8 to -16.9
3300 RAM w/o barriers
-1.11 to -1.21
-13.09 to -13.19
3300 RAM w/ barriers
-1.0 to -1.1
-1.11 to -1.21 *
-12.3 to -12.4
3300 16mm HTPS w/o barriers
-1.6 to -1.7
-18.0 to -18.1
Note: Assume ±50 mV accuracy for check tolerance.
* = BNC Internal Barrier I/O Modules.