3500/42 Operation and Maintenance
Configuration Information
11
Reference Information
These fields contain information that indicates which module you are configuring.
Slot
The location of the monitor in the 3500 rack (2 through 15).
Rack Type
The type of Rack Interface Module installed in the rack (Standard or TMR).
Configuration ID
A unique six character identifier which is entered when a configuration is
downloaded to the 3500 rack.
Slot Input/Output Module Type
The I/O field lets you identify the type of I/O Module that is attached to the
monitor (The option selected must agree with the I/O module installed).
Discrete I/O
Used when each Proximitor/Seismic Monitor and a Proximitor/Seismic
Discrete I/O Module are installed for a standard or nonredundant application.
Discrete Internal I/O
The transducer field wiring is connected directly to the I/O module.
Discrete External I/O
The transducer field wiring is connected to an External Termination Block and
then routed from the External Termination Block to the I/O module through a
25-pin cable. The recorder field wiring is connected to an External
Termination Block and then routed from the External Termination Block to the
I/O module through a 9-pin cable.
Prox/Accel Internal Barrier I/O
The transducer field wiring is connected directly to the Proximitor/Seismic
Monitor Internal Barrier I/O Module. Note that selecting the Prox/Accel
Internal Barrier I/O option will disable certain transducer type options.