Maintenance
3500/42 Operation and Maintenance
94
The following figures show how the Verification screen displays output from a 3500 rack:
Alarm Verification Fields:
These fields display output for verifying channel alarms. Alert/Alarm 1 alarms
are displayed in yellow in the bar graph and with the word “Alarm” under the
current value box. Danger/Alarm 2 alarms are displayed in red in the bar graph
and with the word “Alarm” under the current value box.
Current Value
The current proportional value is displayed in this box.
Setpoints are indicated by lines on the bargraph display:
Danger/Alarm 2 Over = Solid Red Line
Alert/Alarm 1 Over = Solid Yellow Line
Alert/Alarm 1 Under = Dashed Yellow Line
Danger/Alarm 2 Under = Dashed Red Line
The Zero Position Voltage is the voltage input that will cause the reading on the
bar graph display and current value box to be zero. The Zero Position Volts
value is displayed in the Zero Position Volts box above each channel value bar
graph.