3500/42 Operation and Maintenance
Maintenance
169
WARNING
Application Alert
High voltage present.
Contact could cause
shock, burns, or death.
Do not touch exposed
wires or terminals.
Tests will exceed alarm
setpoint levels causing
alarms to activate. This
could result in a relay
contact state change.
Application Alert
Disconnecting the field
wiring will cause a not
OK condition.
Test Equipment Setup - Acceleration
Simulate the transducer signal by connecting the power supply, function
generator, and multimeter to COM and SIG / A of channel 1 with polarity as
shown in the figure on page 170 (Acceleration Test Setup). Set the test
equipment as specified below.
Power Supply
Function Generator
-6.50 Vdc
Waveform: sinewave
DC Volts: 0 Vdc
Frequency: 100 Hz
Amplitude level: Minimum (above
zero)