3500/42 Operation and Maintenance
Configuration Information
25
range and the upscale direction.
- Monitors must be configured in channel pairs (for example, Channels 1 and
2 may be configured as Thrust Position and Channels 3 and 4 may be
configured as Radial Vibration).
- When a full-scale range is modified, the setpoints associated with this
proportional value should be readjusted.
- If a Non-Standard transducer is selected, the setpoint OK limits are set to
±1 volt from the Upper and Lower OK limits that are selected.
- There are two selections for 3000 Series transducers:
3000(-24V) Proximitor
Select this option when connecting a 3000 Series proximitor directly to a
3500 monitor. A default scale factor of 285 mV/mil will be selected. This
may be adjusted ±15 %. Note that the buffered transducers on the front
of the monitors and to the Data Manager are not compensated and
should be interpreted at 285 mV/mil.
3000(-18V) Proximitor
Select this option when connecting a 3000 Series proximitor directly to a
3500 monitor, but supplying proximitor power from an external 18 volt
source. A default scale factor of 200 mV/mil will be selected. This may
be adjusted ±15 %. Note that the buffered transducers on the front of the
monitors and to the Data Manager are not compensated and should be
interpreted at 200 mV/mil.