3500/42 Operation and Maintenance
Configuration Information
63
Customize button
Used to adjust the Scale Factor for standard transducers. If Non-standard is
selected as the transducer type, the Scale Factor and the OK Limits can be
adjusted. The Non-standard transducer's scale factor must be between 90
and 575 mV/mil. Also, there must be at least 2 volts between the Upper and
Lower OK Limits.