3500/42 Operation and Maintenance
Maintenance
175
5.1.9.5
Calculating Verification Frequency
The procedures for verifying channel values and corner frequencies require that
you use the following formulas to calculate the verification frequency.
Find the center of the Band-pass frequency range. Input the configured high-
pass filter corner frequency and the low-pass filter corner frequency into the
formula below:
Frequency = (0.89
×
HPF) + (0.1575
×
LPF)
HPF = High-pass Filter Corner Frequency
LPF = Low-pass Filter Corner Frequency
If no filtering is configured, set the frequency of the function generator to 100 Hz.
If a low-pass filter is configured and no high-pass filter is configured, use the
following to determine the HPF to use in the formula:
-
If the units are integrated or rms, use a HPF of 10 Hz. For any other
configuration, use a HPF of 3 Hz.
If a high-pass filter is configured and no low-pass filter is configured, use the
following to determine the LPF to use in the formula:
-
If the configuration is a single channel with no integration, use a LPF of
30 kHz.
-
If the configuration is a single channel with integration, use a LPF of 14.5
kHz.
-
If the configuration is a dual channel pair, use a LPF of 9.155 kHz.
5.1.9.6
Calculating the Input Voltage for Full-scale
The procedures for verifying channel values and corner frequencies required that
you use the following formulas to calculate the input voltage for full-scale. To
find the full-scale input voltage, use appropriate table for integrated or non-
integrated units.
Note
Use the transducer scale factor displayed in the Scale Factor Box on the
Verification screen.