Specifications
3500/42 Operation and Maintenance
216
ELECTROMAGNETIC COMPATIBILITY
Note: The 3500 Monitoring System conforms to the specifications listed
below. The specific test setup, test levels, and pass criteria (monitor
accuracy) for these tests are defined in the 3500 Technical Construction File.
For copies of this file, contact your local Bently Nevada office.
EN50081-2:
Radiated Emissions:
EN 55011, Class A
Conducted Emissions:
EN 55011, Class A
EN50082-2:
Electrostatic Discharge:
EN 61000-4-2 (1995), Criteria B
Radiated Susceptibility:
ENV 50140 (1993), Criteria A
Conducted Susceptibility:
ENV 50141 (1993), Criteria A
Electrical Fast Transient:
EN 61000-4-4, Criteria B
Surge Capability:
EN 61000-4-5, Criteria B
Magnetic Field:
EN 61000-4-8, Criteria A
Power Supply Dip:
EN 61000-4-11, Criteria B
Radio Telephone:
ENV 50204, Criteria B
HAZARDOUS APPROVALS
CSA-NRTL/C:
When used with
Internal/External Termination
I/O Module
When used with Internal
Barrier I/O Module (Internal
Termination) *
Class I, Division 2, Groups A through D
Class I, Division 1, Groups A through D
Class II, Division 1, Groups E, F, G
Class III
* Hazardous Approvals for Class I, Division 2, Groups A through D Pending.
CENELEC:
When used with Internal
Barrier I/O Module (Internal
Termination)
[EEx ia] IIC