Configuration Information
3500/42 Operation and Maintenance
56
Transducer
Scale Factor
Without
Barriers
With Bently
Nevada Internal
Barriers
Standard I/O
With
Barriers
Discrete TMR
I/O With
Barriers
Bussed TMR
I/O With
Barriers
23733-03
100 mV/g
100 mV/g
95.6mV/g
100 mV/g
99.4 mV/g
24145-02
100 mV/g
*
*
*
*
330400
100 mV/g
100 mV/g
95.6mV/g
95.6 mV/g
95.6 mV/g
330425
25 mV/g
25 mV/g
23.9mV/g
23.9 mV/g
23.9 mV/g
49578-01
25 mV/g
25 mV/g
23.9mV/g
25 mV/g
24.9 mV/g
155023-01
25 mV/g
*
*
*
*
Note: ±15 % scale factor adjustment allowed.
* Barriers are not supported with this transducer option.
OK Limits
Upper
Lower
Center Gap Voltage
Transducer
Without
Barriers
(V)
With
Barriers
(V)
Without
Barriers
(V)
With
Barriers
(V)
Without
Barriers
(V)
With
Barriers
(V)
23733-03
-15.05
-13.85
-15.05
†
-2.75
-3.10
-2.75
†
-8.90
-8.475
-8.90
†
24145-02
-15.05
*
-2.75
*
-8.90
*
330400
-15.05
-13.85
-15.05
†
-2.75
-3.10
-2.75
†
-8.90
-8.475
-8.90
†
330425
-11.37
-10.86
-11.37
†
-5.63
-5.34
-5.63
†
-8.50
-8.10
-8.50
†
49578-01
-11.37
-10.86
-11.37
†
-5.63
-5.34
-5.63
†
-8.50
-8.10
-8.50
†
155023-01
-11.37
*
-5.63
*
-8.50
*
* Barriers are not supported with this transducer option.
†
BNC Internal Barrier I/O Modules.
Transducer Jumper Status (on I/O Module)
Returns the position of the Transducer Jumper on the Proximitor/Seismic I/O
Module. Refer to Section 4.1 (Setting the I/O Jumper)for the function of this
jumper.
Alarm Mode
Latching
Once an alarm is active, it will remain active even after the proportional value
is no longer in alarm. The alarm state will continue until the channel is reset.
See Page 46.