9.4.3 Configuration Assembly Object
The iVuPlus EIP implementation does not support an assembly object configuration instance. However, one is required for creation of
implicit Class 1 connections on a ControlLogix family PLC. Therefore, a configuration instance is defined as instance number 0x80 (128
decimal). It's size is zero.
9.4.4 Data Formats
The iVuPlus EIP implementation supports 32-bit Integers in LSW_MSW data format. The least significant word is stored first, then the
most significant word. This format is used for Allen-Bradley ControlLogix PLCs.
The string format is compatible with the Allen-Bradley ControlLogix built-in string data type. This format is a 32 bit (DINT) length followed
by character bytes (SINT). This results in the following string format as viewed from the iVu Plus:
9.4.5 Minimum Requested Packet Inverval (RPI) Value
iVuPlus devices can operate with input and output Requested Packet Intervals (RPIs) as low as 50 milliseconds. The device may not
operate reliably if a lower RPI value is selected.
iVu Plus BCR User's Manual
Rev. B
www.bannerengineering.com - tel: 763-544-3164
119