4.1.1 Common Configuration for Switch Channels
Any switch input channel can be configured to either be used as a configurable input
function, or as an ordinary channel.
If a function is configured, the DCU will automatically disable the ordinary channel
use.
Function
Whenever a function is configured, that function will be assigned to the switch channel. The
following functions are available for the switch channels. The
highlighted
functions are the
most typically being used.
The function is activated when the input is connected to 24V. The function is deactivated
when the input is left open, or connected to 0V.
Function Name
Description
None
The channel is being used as an (ordinary)
engine sensor switch input.
Local Mode
Sets the panel to local mode, meaning all
external commands are blocked.
Remote Mode
Sets the panel to remote mode, meaning all
local commands are blocked.
Backlight 100%
Force backlight to 100%
Prelube Override
The configured prelube sequence is aborted.
Prelube Complete
Signal shall come from the prelube system,
notifying the panel that the prelube sequence is
completed. The panel will leave the prelube
phase and commence start.
Start Disabled
Start is disabled.
Automatic Mode
210E only. The panel accepts automatic
start/stop signals.
Page 19 (99)