If the Secondary Starter is enabled, a 2nd crank output needs to be configured on
an output.
Cranking Time
and
Delay Between Start Attempts
are the same as for Starter 1.
When Starter 2 is enabled, start modes can be selected under the General section.
Automatic Stop
The DCU can stop the engine automatically. In order for an automatic stop to begin the DCU
must be in automatic mode, and an automatic stop request must be initiated (for instance
terminal 90 on DCU 410E).
Delay Before Disconnecting Generator Breaker
sets the time the DCU will wait when an
automatic stop is initiated before disconnecting the generator breaker, if any. Typical setting
is 1 - 60 seconds.
The Disconnect Generator Breaker signal is not a standard output signal, and
must be configured to a suitable 24V or relay output.
Cooling Time
sets the time the engine will continue to run (with no load) to cool down. When
the timer has elapsed, the DCU will stop the engine. Typical setting is 1 - 5 minutes.
Stopping
Configurable settings for stopping.
Stopping Time
sets the time for the duration of the stop sequence before issuing a stopping
failure event.
Safety Stopping Time
is the time for the duration of safety stopping, where the DCU has lost
all run indications.
Time Hysteresis for Unsolicited Stopped
is the configurable time for which the engine speed
needs to be below 5 RPM in order to transition to stopping from a running state.
7 Communication
All the panel communication interfaces.