Service Interval
One of the configured
service intervals are due
Engine Protection
Override
The panel is in shutdown
override state, and
shutdown channels are
now alarming only.
Overspeed setpoint is
always enabled.
Engine Protection
Override
/Emergency Mode
Same as “Engine
Protection Override” but
also with Emergency
mode activated.
Power on
The panel is powered
Power off
The panel is powered off
Supply Voltage
Low
The supply voltage is
below the fixed setpoint.
Note different setpoints
for 12V and 24V systems.
Speed Relay 1, 2,
3, 4
The function activates at
the configured rpm value
Alarm or Ack
Button or Remote
Acknowledge
The panel is being
acknowledged and the
buzzer is silenced
Common Start
Failed
Start or crank failure
Common Stop
Failed
Stop failed. A
configurable timer
(Engine Stopping Time)
passed without the engine
stopping.
Start, Stop, Alarm,
Up, Down, Home
Button
Individual buttons pressed
Soft Button 1, 2, 3,
4
One of the soft buttons at
the bottom of the screen
is pressed
Ready To Take
Load
Engine rpm is above the
setpoint
Ready for PMS
Start
Panel is ready for power
management start:
- Panel is in Auto
- Panel is not in Local
- Panel supply V. is OK
- Panel is in Ready state
In Gear
In gear
On Secondary
Supply
Panel is running on
secondary supply
New Alarm Pulse
Whenever a new event
appears in the alarm list,
this function activates for
a second, then
de-activates automatically
In Manual Mode
Panel is in manual mode
and will not start
automatically
In Automatic Mode Panel is in automatic
mode
Primary Power
Failure
Primary power failure
Secondary Power
Failure
Seondary power failure
Overspeed
Engine rpm is above
configured setpoint for
overspeed
ETR
Energize to Run. Active
when engine cranks or
runs.
ETS
Energize to Stop.
Activates when engine is
stopping
Load Reduction
Load reduction active
Shutdown
Engine is being stopped
automatically from a
sensor input, including
overspeed
Running
Engine is running
Crank
Panel is cranking/ starting
the engine
Prelube Activation The panel has activated
the prelube function
J1939 <State>
Individual states of SPN
3543
Emergency
start/mode
Panel is in emergency
mode, or an E-Start
sequence is activated
Page 51 (99)