The DCU has a primary and a secondary power supply
input.
If the secondary input is not in use, the low voltage alarm
on this input needs to be disabled.
Primary Power Fail Alarm Enabled
Set to No to disable the alarm. This is used when
there is no connection to the primary supply.
Set to Yes to enable the alarm. This is used when
there is a connection to the primary supply.
Typical setting:
Yes. Normally, there shall be a separate supply
connected to the primary supply.
Secondary Power Fail Alarm Enabled
Set to No to disable the alarm. This is used when
there is no connection to the secondary supply.
Set to Yes to enable the alarm. This is used when
there is a connection to the secondary supply.
Typical setting:
Yes. Normally, there shall be a separate supply
connected to the secondary supply.
J1939 CAN bus Broken Wire Alarm When Engine Not
Running
Default setting is No.
J1939 CAN bus Nodes Lost Warning Enabled:
Default setting is No.
Erratic J1939 Data Warning Enabled:
Default setting is No.