400 Series Installation and Configuration
DCU 410 Engine Panel Installation
51
Use
DCU
RP
Config.
outputs
Display
Event
Display
Event
RP
x
x
RP + Event
x
x
x
DCU+RP
x
x
x
DCU + RP + Event
x
x
x
x
x
Silent Event
x
DCU + Silent Event
x
x
RP + Silent Event
x
x
DCU + RP + Silent Event
x
x
x
Display = the signal is displayed in a gauge, or a numerical format.
Event = warning, alarm or shutdown.
Silent Event = no local event, but event on communication only.
Note! Normally, and in most cases, the selection should
be “DCU + RP + Event”, as
highlighted in the table above.
This makes sure the channel is displayed in the DCU and
in the RP, if
–
or when
–
the RP is installed.
Sensor
Sensor Unit
Select the unit, as printed on the sensor. An oil
pressure sensor might for instance be in Bar or psi.
Sensor Range Min and Max
Select the sensor range values for min and max, as
printed on the sensor.
Display
Display Unit
For the above sensor, select the desired displayed
unit for US and Metric values.
Display Range Min and Max
For the above sensor, select the desired minimum
and maximum values displayed in the instrument,
for US and Metric values.