400 Series Installation and Configuration
DCU 410 Engine Panel Installation
33
The Administration folder is password protected by a
password. It will remain open for 60 minutes after valid
password.
Use the
up / down arrows
to select each of the four
groups of numbers and press
edit
to edit each group.
IP-address convention
The factory default IP of the DCU is 192.168.0.101. The
first three groups must be the same for all components in
the LAN, for instance 192.168.0.X, where X is the other
unit in the LAN.
Note! The X-figure must be unique within the LAN. Also,
the two last digits in X will represent the engine number.
Example: A DCU with the IP-address 192.168.0.104 will
be named
“
Engine
#4”.
Connect the DCU to a single PC
First,
make sure that the PC’s Ethernet ne
twork
configuration is set to automatically receive an IP-address
(as most PCs are). Then in the DCU panel menu:
Menu /Settings
Connect a PC…
Press the down arrow and then Toggle. The DHCP-server
will now be active for 10 min. Repeat if it takes longer
than 10 min to ready the PC.
Connect the PC to the DCU with a CAT-5 Ethernet cable.
The DCU
’s DHCP
-server will now automatically set up the
PC to communicate with the DCU. It may be necessary to
use a network reset/repair function for the
PC’s
Ethernet
connection in order for the PC to receive the new IP-
address.
Alternatively, set the IP-address of the PC manually to a
free IP-address in the same subnet as the DCU.
For instance, if the
DCU’s
IP-address is 192.168.0.101,
the PC may use any IP-address starting with 192.168.0
except 192.168.0.101.