DCU 410 Engine Panel Installation
400 Series Installation and Configuration
The Start and Stop button can be configured to be
Latched
or
Momentary
.
Note! The selection is valid for the Start and Stop button.
Disable Local Start/Stop Buttons
Disable the local start/stop buttons on the DCU.
Hold Button to Start/Stop
Set to Yes for a momentary Hold-To-Start/Stop
button. The button must be pressed until the
engine has started/stopped.
Set to No for a latched button. The button needs to
be pressed momentarily, after which the DCU
completes the start/stop sequence as if the button
was held continuously.
Typical setting:
No (gives a latched button operation, which is
normally preferred).
Allow E-Start
This will give the option of starting with prelube override
and shutdown override.
Only Allow Local Start In Local or Emergency Mode
Typical setting is Yes.
If setting is No, local start/stop will work in any mode of
operation.
Allow Automatic Start/Stop in All Operation Modes:
Default setting NO.
Prohibit Crank Above RPM Threshold [RPM]
Select between
Not in use