54
DCU 410 Engine Panel Installation
400 Series Installation and Configuration
If two or more engine speed (pickup)
sources
2
are in use, then it is
recommended leaving this off for all
switches. Set to
No
.
If one engine speed source only,
locate the engine oil pressure switch
and use this as the Additional Run
signal. Set to
Yes
.
PT100
First, select any of the four PT100 channels.
Then, for each selected channel, set the parameters, as
for the 4-20 mA section, page 50.
24V Inputs
First, select any of the two 24V input channels.
Note! These are
fixed function
inputs, and not the general
switch input channels, as described on page 45.
These two inputs can be given a function from a list of
available functions. The current available functions are:
Local Mode
Remote mode
Backlight 100%
Prelube Override
2
An engine speed source can be the magnetic pickup connected to the DCU,
the J1939 CAN bus signal connected to the DCU, or the speed signal coming
from the connected SDU 410 safety unit.