68
DCU 410 Engine Panel Installation
400 Series Installation and Configuration
Override Allowed
Select if a prelube should be possible to manually
override, to continue the start sequence with an
incomplete prelube sequence.
Note! The override is done in the DCU menu
–
Settings
–
Prelube Override.
Action Upon Timeout
Select the action if the Prelube Timeout timer elapses.
Select Allow Start to continue cranking the engine
anyway.
Select Abort Start to abort the start sequence. The
DCU will indicate with a Prelube Failure alarm.
Oscillating
The DCU can prelube the engine continuously, in a never
ending sequence. The sequence is disabled while the
engine is running.
Oscillating Enabled
Set to Yes to enable oscillating prelube.
Oscillating On Time
Set the number of seconds the DCU shall lubricate the
engine.
Typical setting:
60 seconds
Oscillating Off Time
Set the number of minutes between each lubrication
action.
Typical setting:
60 minutes
Oscillating Feedback
Set this if a feedback from the oscillating feedback is
required. The feedback will have to be connected to
prelube complete.