400 Series Installation and Configuration
DCU 410 Engine Panel Installation
47
Switch
First, select any of the eight switch channels. Then, for
each channel, set the following parameters.
General
Channel Use
Set to Event if in use. An event can be a warning,
an alarm or a shutdown scenario.
Set to Silent
Event for an active channel, but no
panel alarms. The event will be available on
communication only.
Event
Select from Warning, Alarm, Load reduction or
Shutdown.
Input State
Select NO (normally open), or NC (normally closed).
NO means the contact must close to make the
event, whereas NC means the contact must open to
make the event.
Note!
Normal
denotes a running engine with no
alarm.
Delay Before Event
Choose the desired persistence time before the
event triggers.
Typical values:
Engine Oil Pressure Low: 2 seconds.
Engine Coolant Temp. High: 5-10 seconds.