104
© 2019, ATEÏS, member of PAX ProAV Group
5.1.7.1.10 Security mode (power saving)
Enter security mode:
o
Auto: If the AC mains power is not present, the controller will switch to DC power (for battery
backup). Once switch to DC power, the system will automatically enter the security mode.
o
Manual: Force the system to enter the security mode.
Power saving for security mode: This option is available for [Manual] mode only.
o
Select [ON] to enter the security mode for system power saving, and let the listed functions
such as Fireman, Route Key etc. which has ticked the [Security] checkbox to be activated
only.
Please note the active functions which are under the security mode can only be activated
unless the [Security] option on their setting window (Event/Paging/Scheduler/Evac input
setting window) is also enabled, see the picture below.
o
If selects [OFF], the system will not enter the security mode for system power saving. In other
words, all the BOUTIQUE functions can be fully operated.
This mode will be automatically canceled if the BOUTIQUE controller is rebooted.
5.1.7.1.11 Power monitor
Allow to monitor the 2 types of power supply of controller (AC mains power and 48VDC battery
backup). When the power input is not connected to the controller, a fault will be recognized by
system, and the fault LED on front panel of controller will light up, output the warning tone, and
record this
fault on fault list and log book.