Configuration
115
© 2019, ATEÏS, member of PAX ProAV Group
is played in zone1, 2 and 3, Alarm message is played in zone4.
Evacuation Input 3 (CH3) activated: If CH1, CH2 and Ch3 are still activated, the Evac
message is played in zone1, 2, 3 and 4, Alarm message is played in zone5.
In order to avoid any sensitivity issue like unwanted triggering of input, you can set a
response time (from 300ms to 5000ms) on Normal Logic inputs or Evacuation Inputs.
5.1.8.2.2 Normal logic inputs
The Normal Logic Inputs (control Inputs) have been designed to work with simple contact, button or
RAC 5/RAC 8. Each logic input channel can be assigned as an event, users need to create the
event before assigning the control function here.
ON/OFF response time: Set the response time to avoid triggering the Evac inputs
accidentally. When the input voltage is continuously above the range of triggering signal, the
event will be triggered by system.
The trigger signal should be at least as long as the response time to activate the
corresponded Evac input. The range of response time is from 300ms to 5000ms. The shorter
the response time has set, the response action will be more sensitivity.
1. Output contact:
o
Close to trigger: The [ON Function] event will be triggered when the evac input is close,
and open to trigger the [OFF Function] event.
o
Open to trigger: The [ON Function] event will be triggered when the evac input is open,
and close to trigger the [OFF Function] event.
2. Latch mode: Set the normal logic input to be in latch mode for this event when connecting to
a latching ON-OFF switch button, it requires to input state from Hi to Low to start the event,
and input state from Low to Hi to stop the event.
3. Type:
o
Button: Trigger the event by a voltage change (Hi/Low). Trigger in Hi and cancel in Low or
cancel in Hi and trigger in Low.
o
Edge Trigger: Trigger the event by [ON Function] event and cancel it by [OFF Function]