Configuration
129
© 2019, ATEÏS, member of PAX ProAV Group
setting first, the security mode is activated when under [Security Mode Manual] mode only.
For example, if the Security mode is enabled in a evac/alarm paging event, this paging event will
continue working even the system is under the power saving mode (sleep mode), see the picture
below.
Evacuation option:
If an paging event with Evacuation option has been triggered, the system will enter the
evacuation mode.
The EVAC LED on the front panel of BTQ-VM4/VM8/SG8/SL8/DPM-T5/CD-T5DF will light
up.
Play the evac messages to the pre-defined zones if the zones has chosen to use the evac
paging source.
The volume of the rotary knobs on BTQ-VM4/8 will bypass, and make sure the volume of
paging does not attenuate.
The 3-wire type of speaker lines will bypass, and make sure the the volume set by the
VAT volume attenuator does not attenuate.
The Evacuation option can be used for all kinds of "play message" event, and on all events
which are related to audio sources.
Enter security mode:
o
Auto: If the AC mains power is not present, the controller will switch to DC power (for battery
backup). Once switch to DC power, the system will automatically operate the security mode.
o
Manual: Select [Manual] mode to allow the system to operate the security mode function.
Power saving for security mode: This option is available for [Manual] mode only.
o
Select [ON] to activate the security mode for system power saving, and let the listed functions
such as Fireman, Route Key etc., to be activated only.
o
If selects [OFF], the system will not activate the security mode for system power saving. In
other words, all the BOUTIQUE functions can be fully operated.
5.1.9
Third party
Allows other devices to control the BOUTIQUE system through 3rd party control.
Event name: The event name is the
triggering code for a 3rd party action, this
triggering code sent from the 3rd party
device must be the same as the [Event
Name] here.
Event enable: Enable/disable the 3rd Party