Heater Units
Description
Imperial
Metric
Maximum Heat Output
515,000
Btu/h
543,325
kJ/h
Maximum Temperature
230°F
110°C
Maximum Fuel Consumption
3.65 Gal/h
13.8 L/h
Burner Fuel Pressure
145 PSI
10.0 Bar
Maximum Outlet Air Flow
3,200 cfm
90.6 m3/
min
Static Pressure
2.3 Inches
Water
Column
0.57 kPa
Voltage – AC
115 VAC
Amperes – AC
24 A
Frequency
60 Hz
Phase
Single Phase
Voltage – DC
12 VDC
Amperes – DC
0.5 A
Troubleshooting
Before performing any troubleshooting procedures, see
‘SAFETY’.
For engine and generator troubleshooting, refer to the Engine
Operator’s Manual and Generator Operator’s Manual, or con-
tact your dealer.
Problem
Possible Cause
Solution
Engine will not
start
Battery dead
Charge battery
Out of fuel
Add fuel to tank
Engine issue
Refer to Engine
Operator’s Manual
Heater unit(s) will
not operate
Breaker(s) off
Turn breaker(s) on
Out of fuel
Add fuel to tank(s)
Heating unit outlet
access door closed
Open heating unit outlet
access door
Fuel valve(s) closed Open fuel valve(s)
Heater unit issue
Refer to Heater Unit
Operator’s Manual
Generator issue
Refer to Generator
Operator’s Manual
For all other issues, contact your authorized dealer.