Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
99
CGCM-DLR Unit Configuration
Chapter
4
•
The following tags determine the points that are shown in this UEL
configuration diagram. These tags are in the configuration table and are set
by the like-named fields on the UEL page. VAR values are negative, which
indicate leading. Configure the VAR and watt tags with increasing real
power values in point 1 through point
x
. These tags define the curve
breakpoints. As shown, the curve continues horizontally left from point 1
and vertically up from point 5. The tags are expressed in watts or VARs
respectively.
–
Point 1 is defined by tags
UEL_Curve_W_Pt1
and
UEL_Curve_VAR_Pt1
–
Point 2 is defined by tags
UEL_Curve_W_Pt2
and
UEL_Curve_VAR_Pt2
–
Point 3 is defined by tags
UEL_Curve_W_Pt3
and
UEL_Curve_VAR_Pt3
–
Point 4 is defined by tags
UEL_Curve_W_Pt4
and
UEL_Curve_VAR_Pt4
–
Point 5 is defined by tags
UEL_Curve_W_Pt5
and
UEL_Curve_VAR_Pt5
•
Validate and Graph button – Updates the graph in the UEL tab after
entering new values.
Related Parameters
•
UEL_En
tag in the Output table
1
2
3
4
5
Real Power, Watts
Reactive Power
, V
ARs