Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
217
Specifications
Appendix
D
Over-excitation Limiting - Offline
Under-excitation Limiting
Manual Excitation Control
Metering
Attribute
Range
Increment
Pickup
0…15 A DC
0.1 A DC
Time delay
0…10 s
1 s
Attribute
Value
Real power
0…100% kW for each of five points
Reactive power
0…100% kVAR for each of five points
Attribute
Value
Range
0…15.0 A DC
Increment
0.1 A DC
Attribute
Range
Accuracy
Generator voltage
57…208V AC
0.2% (50/60 Hz)
Generator current
0…5 A AC
0.2% (50/60 Hz)
Generator frequency
10…90 Hz
±0.05 Hz
Bus voltage
57…208V AC
< 0.2% (50/60 Hz)
Bus frequency
10…90 Hz
±0.05%
Phase angle
±180°
±1.0°
Field voltage
0…200V DC
±1.25V or ±1.0% (whichever is
greater)
Field current
0…30 A AC
±0.15 A or ±1.0% (whichever is
greater)
Power factor
-0.5…0.5
<0.4% of actual PF
Power - real and reactive
0…200% of nom
<0.4% of rated kVA
Load share
Resolution: 0.001 per unit percent
Range: 0…5 V
Load Share entity parameters
LS(+)
LS(-)
Ui = 7V DC
Ii = 160 µA
Pi = 28 µW
Ci = 10 nF
Li = 0 H
Uo = 7V DC
Io = 160 µA
Po = 28 µW
Co = 175 µF
Lo = 1 H